Our team supplied and installed a brand new, compliant distribution board in Cannock.

Firstly, we investigated the constant tripping of electrics on site at our clients in Cannock. Upon carrying out our investigations, we identified that the site had a common 30mA RCD in mains distribution board which did not comply and was causing intermittent power outage/nuisance tripping when an increase of current passed through the site, i.e. when 3 or 4 pumps were running simultaneously.

We were asked to provide a solution which would resolve the issue for our client and prevent unnecessary disruptions to site.

So from this, we supplied and installed a compliant distribution board complete with individual 30mA RCD protection and double pole isolation to tank dispensers, control systems and local dispenser lighting. This has rectified the issue and the client is happy to now be running back at full capacity.

Latest News

View all

The Hidden Costs of Skipping Electrical Inspections in Hazardous Areas

June 2025

When it comes to managing a facility with a hazardous area, it can be all too easy to delay inspections to save time or reduce short-term costs. However, this small postponement can lead to much greater long-term costs.

Read more about The Hidden Costs of Skipping Electrical Inspections in Hazardous Areas Share Share on Twitter Share on LinkedIn

Hazardous Areas: The Role of Facility Management in Risk Prevention

May 2025

Facility management professionals play a critical role in ensuring that hazardous areas within the properties they manage are properly maintained and compliant with relevant safety standards.

Read more about Hazardous Areas: The Role of Facility Management in Risk Prevention Share Share on Twitter Share on LinkedIn

Latest Projects

View all

Hazardous Area Lighting For A Hydrogen Dispensing Area

We were contacted to supply and install zone 1 hazardous area lighting to our clients’ hydrogen dispensing area.

Read more about Hazardous Area Lighting For A Hydrogen Dispensing Area

Waste Management Plant Room ATEX Lighting

For a client with a waste management plant room, we supplied and installed zone 1 ATEX certified lighting as well as emergency lighting controls via ATEX certified motion sensor controllers.

Read more about Waste Management Plant Room ATEX Lighting

ISO9001, ISO14001, ISO45001 CHAS APEA ECA CompEx NICEIC Approved Contractor NICEIC Hazardous Achilles Ecovadis